KELCO D50 Calibration Download Page 1

Kelco D50 & D40 Level Switch Calibra

Ɵ

 on

The Kelco D50 and D40 level switches are factory calibrated to operate with the displacer or 
displacers supplied with each switch.  If required, the switch can be re-calibrated by adjus

Ɵ

 ng 

the calibra

Ɵ

 on screw located on the top deck of the switch.  The calibra

Ɵ

 on screw is an M3 Allen 

head stainless grub screw secured with a lock nut and sealed with red enamel.  

D50 Level Switch

The D50 level switch is supplied with two displacers.  If the D50 level switch fails to operate on 
a falling level, that is, fails to switch when the falling water level uncovers the bo

Ʃ

 om displacer 

then the switch will require re-calibra

Ɵ

 on.  It such a situa

Ɵ

 on unlock the calibra

Ɵ

 on screw lock 

nut and wind the calibra

Ɵ

 on screw ¼ turn an

Ɵ

  clockwise and re-lock the lock nut.  Test the switch 

on a falling water level and ensure it operates properly.  If it fails to switch, adjust the sensi

Ɵ

 vity 

screw a further ¼ turn an

Ɵ

  clockwise and repeat the test.

If the switch fails to operate on a rising level, that is, fails to switch when the top most displacer 
is covered by water it will require re-calibra

Ɵ

 ng.  Unlock the calibra

Ɵ

 on lock nut and turn the 

calibra

Ɵ

 on grub screw ¼ turn clockwise and re-

Ɵ

 ghten the lock nut.  Test the switch on a rising 

water level.  If it fails to switch when the top displacer is covered by water, wind the calibra

Ɵ

 on 

screw a further ¼ turn clockwise and repeat the test. 

D40 Level Switch

The D40 level switch has a single displacer and switching must occur within the length of the 
single displacer.  When correctly adjusted the switch should change state at the bo

Ʃ

 om edge of 

the conical sec

Ɵ

 on on a rising level and at the seam line half way down the straight sec

Ɵ

 on on 

a falling water level.   If a rising water level fails to actuate the switch when the displacer is fully 
submerged recalibrate the switch by adjus

Ɵ

 ng the calibra

Ɵ

 on screw clockwise in ¼ turn steps 

un

Ɵ

 l the switch operates at the correct point.

 If the switch fails to operate on a falling water level adjust the calibra

Ɵ

 on screw an

Ɵ

  clockwise by 

¼ turn and retest it.  If required repeat the adjustment un

Ɵ

 l the switch operates properly.    

Calibration adjustment screw and lock nut (M3)