CP 503/A, CP 505/A,D,K, CP 507/
A,C
Diagnosis
Project engineering manual V1.06
66
© KEBA 2021
1) If desired, connect an empty USB stick to the CP 50x/x.
2) Use a short keystroke to change to the
display on the 7-segment dis-
play.
3) Then trigger a status report with a long keystroke. The status report is
written to the CompactFlash card in the
/masterdisk/protocol/sta-
tusreport
directory.
4) If the status report is to be copied to a USB stick, change to the
dis-
play on the 7-segment display using a short keystroke.
5) Save the status report to the main directory of the USB stick using a long
keystroke.
The status report is triggered and copied to the USB stick. Once the status
report has been written, the system will automatically return into the previous
main operating mode.
9.4
Crashreport
If a system error (e.g. "unhandled exception") occurs, a crash report file is
automatically created and saved to a removable storage device of the con-
trol. Upon the next control start-up, it is checked whether a new file is
present. If yes, corresponding messages are issued in the message system.
In general, it must be ensured that the messages are acknowledged. The
crash report file can be saved to a USB stick over the 7-segment display of
the control using
.
Remedy for recurring errors
To fix recurring errors,, the control process must be ended and the applica-
tion deleted. To do so, first navigate to
on the 7-segment display using a
short keystroke and select it using a long keystroke. As a result, there is no
longer an application on the control and the control process can be restarted
on the 7-segment display using
. A new application can then be loaded on
the control.