3-30
Operating Instructions CDF3000
3 Installation
3.11
Control con-
nections
Step
Action
Comment
1
Please check whether you already
have a
S
MART
C
ARD
or a
D
RIVE
M
ANAGER
dataset
with a complete device setup
available, i.e. the drive has already
been planned as required.
2
If this is the case, a special control
terminal assignment applies. Please
contact your project engineer to obtain
the terminal assignment.
Bulk customers
For details of how to load the data
set into the positioning controller
refer to chapter 4.2.
3
Choose a terminal assignment.
Initial commissioning
There are various pre-set solutions
available to make it easier to
commission the device.
4
Wire the control terminals with
shielded cables.
Only the signals ENPO, ISDSH and a
start signal (control via terminal) are
strictly required.
Earth the cable shields over a wide
area at both ends.
Wire cross-section maximum
1.5 mm² or two strands with
0.5 mm² per terminal
Length for stripping insulation 7
mm.
5
Keep all contacts open
(inputs inactive).
6
Check all connections once again!
Continue with commissioning in
section 4.
Please note:
• Always wire the control terminals with shielded cables.
• Lay the control cables separately from the mains lead and motor
cable.
• The CDF3000 Application Manual presents more preset drive
solutions.
• A cable type with double copper braiding with 60 - 70% coverage
must be used for all screened connections.
Summary of Contents for CDF3000
Page 1: ...Positioning controller Rated current 8 A Power supply 24 48 V DC CDF3000 Operation Manual...
Page 12: ...Operating Instructions CDF3000...
Page 16: ...1 4 Operating Instructions CDF3000 1 Safety...
Page 54: ...3 34 Operating Instructions CDF3000 3 Installation...
Page 78: ...4 24 Operating Instructions CDF3000 4 Commissioning...
Page 84: ...5 6 Operating Instructions CDF3000 5 Troubleshooting...