3-16
Operating Instructions CDF3000
3 Installation
3.7
CAN
open
-inter-
face X5
The CAN
open
-interface is integrated in the positioning controller. It is con-
nected via connector X5. The customer is responsible for providing a
power supply to the isolated connection.
Table 3.9
Connection CAN
open
- interface
Assignment of terminal X5:
Table 3.10
Pin assignment X5
The CAN-bus node address is set via coding switch S1.
Connection
Miniature D-Sub 9-pin
Wave terminating resistor
- Bus termination -
120
Ω
(internal)
to be wired by customer via bridge
(Pin 1-2)
Max. incoming frequency
1 MHz
Ext. Voltage supply
Protective extra-low voltage (PELV) with safe
isolation in accordance with EN 50178
+ 24 V +10% / 100 mA
(potential-free to drive controller)
543
2
1
9
8
76
X5
CANopen
Pin
Function
1
Wave terminating resistor 120
Ω
internally for CAN
by bridge between PIN 1 and Pin 2
2
CAN_LOW
3
CAN_GND
4
CAN-SYNC_LOW This pin can optionally be switched by the
micro controller as input or output.
5
Wave terminating resistor 120
Ω
internally for CAN-SYNC
by bridge between PIN 4 and Pin 5
6
CAN_GND
7
CAN_HIGH
8
CAN-SYNC_HIGH This pin can optionally be switched by the
micro controller as input or output.
9
CAN_+24 V (24 V ±10%)
Summary of Contents for CDF3000
Page 1: ...Positioning controller Rated current 8 A Power supply 24 48 V DC CDF3000 Operation Manual...
Page 12: ...Operating Instructions CDF3000...
Page 16: ...1 4 Operating Instructions CDF3000 1 Safety...
Page 54: ...3 34 Operating Instructions CDF3000 3 Installation...
Page 78: ...4 24 Operating Instructions CDF3000 4 Commissioning...
Page 84: ...5 6 Operating Instructions CDF3000 5 Troubleshooting...