3.3.9 fan
Unit size
12
13
14
Heat sink fan
Number
1
Speed-variable
—
Table 22: Fan
NOTICE
Destruction of the fan!
►
Take care that no foreign substances drop into the fan!
3.3.9.1 Switching behaviour of the fan
The fan has different switch-on and switch-off points. The switching point for the switch-
on temperature
①
of the fan is adjustable. The switching point for the switch-off temper-
ature
②
cannot be changed and is always 5°C below the switch-on temperature.
0
20
40
60
80
100
0
20
40
60
50
70
90
80
100
30
10
①
②
Temperature / °C
Fan speed / %
Legend
Temperature curve
Setting range for the switch-on temperature
①
Switch-on point
②
Switch-off point
Figure 8:
Switching behaviour of the fan
3.3.9.2 Switching points of the fan
The switching point for the switch-on temperature is adjustable between 0.1°C and
50°C. The default value is 50°C.
39