3.3.7 Dc link / braking transistor function
Unit size
12
13
14
DC link rated voltage @
U
N
= 400 V
U
N_dc
/ V
565
DC link rated voltage @
U
N
= 480 V
U
N_dc_UL
/ V
672
DC link voltage working voltage range
U
in_dc
/ V
260...750 ±0
DC switch-off level „Error! Underpotential“
U
UP_dc
/ V
240
DC switch-off level „Error! Overpotential“
U
OP_dc
/ V
840
Rated current DC
@
U
in_dc
= 565 V
I
in_dc
/ A
16
20
26
Rated current DC @
U
in_dc
= 680 V
I
in_dc_UL
/ A
13
19
22
Rated current DC
@
U
out_dc
= 565 V
I
out_max_dc
/ A
16
20
26
Rated current DC
@
U
out_dc
= 680 V
I
out_max_dc_UL
/ A
13
19
22
DC switching level braking resistor
1)
U
B_dc
/ V
780
Max. braking current
I
Bmax
/ A
28
34
34
Min. brake resistance value
R
Bmin
/ Ω
33
25
25
DC link capacity
C
/ uF
470
560
680
Protection function for braking transistor (GTR7)
2)
—
Table 20:
DC link / braking transistor function of the 400 V units
1)
The DC switching level for the braking transistor is adjustable. The default value is the value spec
-
ified in the table.
2)
No protective function,
“Wiring of an intrinsically safe braking resistor”.
NOTICE
Destruction of the drive converter if the value has fallen below the
minimum brake resistance value
►
The minimum brake resistance value must not fall below!
Net
Rectifier
DC link
Inverter
Braking
transistor
(GTR7)
Motor
DC Out
Braking
resistor
DC in
I
in
I
N
I
out_dc
I
B
I
in_dc
Figure 7:
Block diagram of the energy flow
Activation of the braking transistor function
The function must be activated with parameter "is30 braking transistor func-
tion" in order to use the braking transistor (GTR7).
Further information can be found in the download area of
.
37
UNIT DATA
Summary of Contents for COMBIVERT S6 Series
Page 2: ......
Page 64: ...64 NOTES ...