Page3.5 - 4
COMBIVERT R6-S
© KEB, 2008-02
Regenerative adjustments
3.5.3 Activate regeneration
The activation of the regeneration is dependent on the reference value of the DC voltage (ru.18) and the re-
generation level cS.02.
The regeneration unit starts to modulate if the DC voltage
exceeds the specified value in cS.02 , which
is per-
cental related to the reference voltage.
Parameter
Addr.
R PG E
Min.
value
Max.
value
Res. [?] Default
cS.02 Regeneration level
0F02h rw
-
-
100
120
1
%
103
3.5.4 Deactivate regeneration
If the active power exceeds the level
specified
in cS.06 the modulation is switched off after puls off delay
(cS.05).
Parameter
Addr.
R PG E
Min.
value
Max.
value
Res. [?] Default
cS.05 Puls off delay
0F05h rw
-
-
0
32000
1
ms
200
Parameter
Addr.
R PG E
Min.
value
Max.
value
Res. [?] Default
cS.06 Puls off level
0F06h rw
-
-
-10000
0
1
kW
-0,8
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......