DIMeNSIONS AND WeIGHTS
3.4.6.2 Mounting distances
Power dissipation for the control cabinet dimension
„3.2.4 Power dissipation at rated oper
. A lower value can be used here depending on the operating mode/load.
Mounting the drive controller
For reliable operation, the drive controller must be mounted without any dis-
tance on a smooth, closed, metallically bright mounting plate.
Mounting distances
Dimen-
sion
Distance in mm
Distance in inch
A
B
D
E
F
C
D
A
150
6
B
100
4
C
30
1.2
D
0
0
E
0
0
X
1)
50
2
1)
Distance to preceding elements in the control cab-
inet door.
Figure 13: Mounting distances
If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriate filters must avoid suction of foreign objects.
Direction of the
airflow
Front and side view of the coolant inlet
Coolant outlet
Coolant inlet
Figure 14:
Control cabinet ventilation