![KEB COMBIVERT F6 series Instructions For Use Manual Download Page 29](http://html.mh-extra.com/html/keb/combivert-f6-series/combivert-f6-series_instructions-for-use-manual_660366029.webp)
3.1.2 Mechanical ambient conditions
Storage
Standard
class
Descriptions
Vibration limits
1M2
Vibration amplitude 0.3 mm (2…9 Hz)
Acceleration amplitude 1 m/s² (9…200 Hz)
Shock limit values
1M2
40 m/s²; 22 ms
Transport
Standard
class
Descriptions
Vibration limits
2M1
Vibration amplitude 3.5 mm (2…9 Hz)
Acceleration amplitude 10 m/s² (9…200 Hz)
(Acceleration amplitude 15 m/s² (200…500 Hz))*
Shock limit values
2M1
100 m/s²; 11 ms
Operation
Standard
class
Descriptions
Vibration limits
3M4
Vibration amplitude 3.0 mm (2…9 Hz)
Acceleration amplitude 10 m/s² (9…200 Hz)
–
Vibration amplitude 0.075 mm (10…57 Hz)
Acceleration amplitude 10 m/s² (57…150 Hz)
Shock limit values
3M4
100 m/s²; 11 ms
Pressure in the water cooler
–
–
Max. operating pressure: 10 bar
Table 3:
Mechanical ambient conditions
*Not tested
3.1.3 chemical / mechanical active substances
Storage
Standard
class
Descriptions
Contamination
Gases
1C2
–
Solids
1S2
–
Transport
Standard
class
Descriptions
Contamination
Gases
2C2
–
Solids
2S2
–
Operation
Standard
class
Descriptions
Contamination
Gases
3C2
–
Solids
3S2
–
Table 4:
Chemical / mechanical active substances
29
TecHNIcAL DATA
Summary of Contents for COMBIVERT F6 series
Page 2: ......