Overload Curves
Load [%]
Permanent
current
(0 Hz)
230V Maximum stall current (amps at 0Hz)
Inverter
Housing
Carrier
Frequency
Inverter Size
13 14 15 15+ 16 17 17+ 19 20 21 23
E
8 kHz
24
24
16 kHz
16.8 16.8
G
8 kHz
33
31
53
16 kHz
33
26
43
H
8 kHz
73
109
97
16 kHz
73
92
59
R
8 kHz
115 145 180
16 kHz
70
102 102
U
4 kHz
319
8 kHz
203
16 kHz
-
480V Maximum stall current (amps at 0Hz)
Inverter
Housing
Carrier
Frequency
Inverter Size
13 14 15 16 17 18 19 20 22 22+ 24 26 26+ 28
E
8 kHz
12 16.5 16
16 kHz
12
10
10
G
8 kHz
19 22.0 21.5
16 kHz
8.4
9.5
-
H
8 kHz
42
50
54
83
16 kHz
25
30
36
45
R
8 kHz
115 150
16 kHz
63
98
U
4 kHz
198 330 330
8 kHz
180 180 225
16 kHz
-
-
-
W
4 kHz
574
8 khz
407
16 kHz
-
At low speeds (below 3 Hz G-W housings, below 6Hz D-E housings), the rms curr
ent flowing
through the power transistors is higher, reaching 1.4 times the rated 60Hz rms value. This is
caused by the low-frequency sine wave created by the PWM. As a result, the continuous output
current must be limited at low speeds to prevent the power transistors from overheating. The
COMBIVERT F5 will drop the carrier frequency to 4kHz if necessary to be able to continue to
provide current to the motor. Once the output frequency rises above low frequency or the current
drops below the levels listed below, the carrier frequency will be returned to the higher value.
2.10 Error Overload Low Speed