L1, L2, L3
3 phase supply voltage
+ +, - -
DC supply connection
+ +, PB
Connection for braking resistor
Housing Size H
Verify input voltage with name plate for proper connection 230V or 480V
T1, T2
Connection for temperature sensor
K1,K2
Brake transistor monitor terminals
U, V, W
Motor connection
PE
Connection for earth ground
Housing Size E
Housing Size G
L1, L2, L3
3 phase supply voltage
++, - -
Connection for DC supply
++, PB
Connection for braking resistor
K1,K2
Brake transistor monitor terminals
T1, T2
Connection for temperature sensor
U, V, W
Motor connection
Connection for earth ground
L1, L2, L3
3 phase supply voltage
++, - -
Connection for DC supply
++, PB
Connection for braking resistor
U, V, W
Motor connection
T1, T2
Connection for temperature sensor
Connection for earth ground
Verify input voltage with name plate for proper connection 230V or 480V
Verify input voltage with name plate for proper connection 230V or 480V
Terminal Tightening Torque: 35 inlbs (4Nm)
Terminal Tightening Torque: 11 inlbs (1.2Nm)
Terminal Tightening Torque: 4.5 inlbs (0.5Nm)
2.7 Summary of the power circuit terminals
L1
L2
L3
++
- -
PB
U V
W
T2
T1
L1 L2 L3 PE
PE ++ - -
PB
PE U
V
W
K1
K2
T1
T2
Power Connections
33