37
Control Connections
To prevent a malfunction caused by interference voltages on the control
inputs, the following steps should be observed:
• Establish a true earth ground for all ground connections!
• Do not connect drive signal commons to earth ground!
• Use shielded cable with twisted pair wires!
• Terminate shield wires to earth ground, only at inverter!
• Separate control and power wires by 8" or more!
• Control and power wires should cross at a right angle!
2.1.2. Connection of
the control signals
EMC
Connect unused analog inputs to common to eliminate noise signals
!
X2A
1 2 3 4 5 6 7 8 9
GND
0...±10 VDC
Ri = 55 k
+
+
0(4)...20 mADC
Ri = 250
*
*
Use of
external
voltage supply
Ri = 2.1 k
Ω
20...30 VDC
Regulated
Use of
internal
voltage supply
2.1.3. Digital Input
Speed Pattern, Torque Command
2.1.4. Analog Inputs