9.3 Technical data of the COMbIVERT F5 AIC devices
Max. precharging AIC at an ambient temperature
T
a
= 45°C and
U
N_max
= 440V / 480V.
Corresponding higher charging currents are expected at higher mains voltages. In this
case please contact KEB!
Size
S
C
int
C
ext_max
at
U
= 440V / 480V
R
Max. exter-
nal charging
current
at
U
= 440V / 480V
Max. total
charging
current
at
U
= 440V / 480V
Notes
AIC
kVA
uF
uF
Ω
A
A
–
14
11
820
–
20
73 / 67
104
NTC as shunt
16
23
1260
–
10
130 / 120
190
18
35
1800
–
20
320 / 315
350
20
52
3900
40.000/35.000
2.5
–
250/270
22
80
4950
40.000/35.000
2.5
–
250/270
24
125
8250
35.000/30.000
2.5
–
250/270
26
173
11700
33.000/27.000
2.5
–
250/270
27
208
14100
30.000/24.000
2.5
–
250/270
28
256
19800
27.000/20.000
5.8
-
107/117
1)
29
319
19800
27.000/20.000
5.8
–
107/117
30
395
39600
140.000/110.000
5.8
1)
-
107/117
1)
33
554
59400
230.000/180.000
3.9
1)
-
161/175
1)
34
616
39600
140.000/110.000
5.8
1)
–
107/117
1)
38
1005 59400
230.000/180.000
3.9
1)
-
161/175
1)
Legend
S
Apparent power
Cint
Internal capacity
Cextmax
Maximum, connectable capacity
R
Load-shunt
Table 20: Technical data of KEB COMBIVERT F5 AIC devices
1)
Option precharging resistor =>
„Additional precharging resistor at master-slave operation“
NOTICE
A restart for AIC with NTC is allowed only after 5 minutes.
61
DIMENSIONING