8.3.2 Description of the RS232/485 interface X6C
X6C
PIN
RS485
Signal Meaning
5 4 3 2 1
9 8 7 6
5 4 3 2 1
9 8 7 6
1
-
-
reserved
2
-
TxD
Transmission signal RS232
3
-
RxD
Receive signal RS232
4
A‘
RxD-A
Receive signal A RS485
5
B‘
RxD-B
Receive signal B RS485
6
-
VP
Supply v5 V
(
I
_max
= 50 mA)
7
C/C‘
DGND
Data reference potential
8
A
TxD-A
Transmission signal A RS485
9
B
TxD-B
Transmission signal B RS485
Table 18:
Description of the RS232/485 interface X6C
8.3.3 Connection of the RS232 interface
A RS232 cable is required to connect the interface operator with a PC.
Serial cable to connect the operator with a PC
0058025-001D
1
5
6
9
1
5
6
9
8.3.4 Connection of the RS485 interface
NOTICE
The following instructions must be observed to prevent malfunctions at
the RS485 interface:
• Use CAT 5 cable (in pairs, twisted and shielded cable)
• Ground to one side (prior to the lower interference side)
•
Attach terminating resistors of 120 Ω to both ends of the bus
If CAT 7 cable is used (by way of derogation from our recommendation) lay the
interior shield each to the transmitter.
If malfunctions still occur, it is possible to use a biasing. However, this shall be
done only once at the bus (preferably at the master).
56
OPERATION OF THE CONTROL