Page 7.1 - 22
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Operating and appliance data
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.11
Baudrate int. Bus
000Bh RW
-
+
3
11
1
-
11
The transmission rate between operator/inverter or PC/inverter is determined with the internal baudrate.
Following values are possible:
Value
Baud rate
Value
Baud rate
Value
Baud rate
3
9.6 kBaud
6
55.5 kBaud
9
115.2 kBaud
4
19.2 kBaud
7
57.6 kBaud
10
125 kBaud
5
38.4 kBaud
8
100 kBaud
11
250 kBaud
After Power-On it is always started with 38.4 kBaud and dependent on the operator higher set.
Parameter
Addr.
R
PG
E
Min. value
Max.
value
Res.
[?]
Default
Sy.17
Proc. read data 1 set
0011h
*
-
+
1
128
1
hex
1
SY.19
Proc. read data 2 set
0013h
*
-
+
1
128
1
hex
1
SY.21
Proc. read data 3 set
0015h
*
-
+
1
128
1
hex
1
Sy.17
Proc. read data 4 set
0016h
*
-
+
1
128
1
hex
1
* rw via bus; r via keyboard
Parameter
Addr.
R
PG
E
Min. value
Max.
value
Res.
[?]
Default
SY.16
Proc. read data 1 defi
-
nition
0010h
*
-
+
-1
7FFFh
1
hex
-1
SY.18
Proc. read data 2 defi
-
nition
0012h
*
-
+
-1
7FFFh
1
hex
-1
SY.20
Proc. read data 3 defi
-
nition
0014h
*
-
+
-1
7FFFh
1
hex
-1
SY.22
Proc. read data 4 defi
-
nition
0016h
*
-
+
-1
7FFFh
1
hex
-1
* rw via bus; r via keyboard
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.32
Scope timer
0020h
RO
-
-
0
65535
1
-
0
The scope timer generates a time period of 1 ms. This can be used by external programs, e.g. scope, to re-
present time patterns. The timer counts from 0...65535 and starts again with 0 after an overflow.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.41
Control word high
0029h
RW
-
+
0
65535
1
-
0
The control word is used for state control of the inverter via bus. The control word long (Sy.43) consists of the
two 16 bit parameters control word high (Sy.41) and control word low (Sy.50). The status word is bit-coded.
The description of the individual bits is found in chapter 10.1.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.42
Status word high
002Ah
RO
-
-
0
65535
1
-
0
With the status word the current condition of the inverter can be readout via bus. The status word long (Sy.44)
consists of the two 16 bit parameters status word high (Sy.42) and status word low (Sy.51). The status word
is bit-coded. The description of the individual bits is found in chapter 10.1.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...