Page 7.1 - 18
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Operating and appliance data
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
In.
17
Temperature mode
0E11h
RO
-
-
0
LTK
1
-
LTK
Parameter In.17 displays in high byte the temperature mode of the inverter. The desired function is adjusted
with Pn.72 and operates in accordance with the following table:
In.
17
Function of T1, T2
Pn.72
Resistance
Display ru.46
Error/ warning
1)
0xh
PTC
(in accordance with DIN
EN 60947-8)
-
< 750 Ω
T1-T2 closed
-
0.75…1.65 kΩ
(reset resistance)
not defined
-
1.65…4 kΩ
(tripping resistance)
not defined
x
> 4 kΩ
T1-T2 open
x
5xh
KTY84 (standard)
0
< 215 Ω
Detection error
x
498 Ω
1°C
-
2)
1 kΩ
100°C
x
2)
1,722 kΩ
200°C
x
2)
> 1811 Ω
Detection error 254
x
PTC
(in accordance with DIN
EN 60947-8)
1
< 750 Ω
T1-T2 closed
-
0.75…1.65 kΩ
(reset resistance)
T1-T2 closed
-
1.65…4 kΩ
(tripping resistance)
T1-T2 open
x
> 4 kΩ
T1-T2 open
x
6xh
PT100
-
on inquiry
1)
The column is valid at factory setting and Ud.02 ≥ 4 (F5-Multi, Servo). At Ud.02 < 4 (F5-General) the
function must be programmed accordingly with parameters Pn.12, Pn.13, Pn.62 and Pn.72.
2)
The disconnection is depending on the adjusted temperature in Pn.62.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
In.22
User parameter 1
0E16h
RW
-
-
0
65535
1
-
0
In.23
User parameter 1
0E17h
RW
-
-
0
65535
1
-
0
This parameters are not assigned to any function and are available to the user for input.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
In.
24
Last error
0E18h
R
-
-
0
255
1
-
-
In.24 stores the 8 errors that occurred last. The display is set-programmable. E. UP is not stored. The error
messages are described in chapter 8. If the value 0 is written, (only possible with supervisor password), all
error messages in all sets are deleted.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...