Operating and appliance data
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.1 - 9
7
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
ru.25
output terminal state
0219h
RO
-
-
0
255
1
-
-
Display of the external and internal digital outputs set currently. According to following table a specific decimal
value is given out for each digital output. If several outputs are set, the sum of the decimal values is indicated.
Bit
-No.
Decimal
value
Output
Terminal
0
1
O1 (transistor output 1)
X2A.18
1
2
O2 (transistor output 2)
X2A.19
2
4
R1 (relay RLA,RLB,RLC)
X2A.24...26
3
8
R2 (relay FLA,FLB,FLC)
X2A.27...29
4
16
OA (internal output A)
no
5
32
OB (internal output B)
no
6
64
OC (internal output C)
no
7
128
OD (internal output D)
no
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
ru.26
active parameter set
021Ah
RO
-
-
0
7
1
-
-
The KEB COMBIVERT can have access to 8 parameter sets (0-7). Through programming the inverter can
change parameter sets autonomously and can thus start different modes of operation. This parameter shows
the parameter set, with which the inverter is operating currently. Independent of it another parameter set can
be edited by bus (also see chapter 7.16).
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
ru.27
AN 1 /
pre amplifier
display
021Bh
RO
-
-
-100
100
0.1
%
-
This parameter indicates the value in percent of the analog signal AN1 on the differential voltage input (ter-
minal X2A.1 / X2A.2) before signal amplification. In dependence on An.10 the indicated value of 0...±100 %
corresponds to An.00: 0...±10 V; 0...±20 mA or 4...20 mA (also see chapt. 7.2 „Analog inputs“).
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
ru.28
AN 1 /
post amplifier
display
021Ch RO
-
-
-400
400
0.1
%
-
This parameter shows the value of the analog signal AN1 in percent after passing the characteristic amplifier.
The range of indication is limited to ±400 % (also see chapt. 7.2 „Analog inputs“).
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
ru.29
AN 2 /
pre amplifier
display
021Dh RO
-
-
-100
100
0.1
%
-
This parameter shows the value in percent of the analog signal AN2 on the differential voltage input (terminal
X2A.3 / X2A.4) before the signal amplification. The indicated value of 0...±100 % corresponds depending on
An.10: 0...±10 V; 0...±20 mA or 4...20 mA (also see chapt. 7.2 „Analog inputs“).
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...