Start-up
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 6.2 - 13
6
6.
Input of the motor data
The values dr.00 to dr.05 must be taken from the motor
name plate.
The values for dr.06 to dr.08 can be taken from the motor
data sheet (if available) or they can be identified automati
-
cally (see point 10).
The DASM head-inductance (dr.10) should always be iden-
tified, because it is dependent on the selected magnetizing
current.
⇒
dr.00 DASM rated current
⇒
dr.01 DASM rated speed
⇒
dr.02 DASM rated voltage
⇒
dr.03 DASM rated power
⇒
dr.04 DASM cos phi
⇒
dr.05 DASM rated frequency
⇒
dr.06 DASM stator resistance
⇒
dr.07 DASM sigma-inductance
⇒
dr.08 DASM rotor resistance
⇒
dr.10 DASM head-inductance
Attention: The interconnection of
the motor must be considered at ac-
ceptance of the values of the motor
data sheet. The data sheet contains
mostly phase values. The phase-pha-
se values must be entered in parame-
ters dr.06...dr.10.
The default values can remain in dr.06
to
dr.10 up to the identification if no
equivalent circuit data are known
7.
Parameterize flux-/rotor adaptation mode
The operation with motor model is activated in parameter
ds.04 flux/rotor adaptation mode.
⇒
dS.04 = 249
Further necessary adjustments for the operation with motor
model are additionally made by this parameter:
• Maximum voltage controller, maximum voltage 100%
(without overmodulation)
• Flux controller and magnetization build-up active before
start-up
Attention: Further adjustments must be
done in connection with the maximum
voltage controller: Parameterization of
the controller,
Activation of the active current limita-
tion in the field-weakening range 7.9.
Further information about the flux con
-
troller and flux build-up see chapter 7.6
Adjustments of the synchronous motor
8.
Calculation of motor-dependent data
Even if the motor data dr.06...10 are unknown, the motor-
dependent data (e.g.
dr.18 field weak. speed) must be cal
-
culated once at this point.
⇒
Fr.10 load motor-dep. parameter = 2: act. DC link vol-
tage
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...