Page 8.1 - 8
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Troubleshooting
Display
COMBIVIS
Value Meaning
E. UP
Error ! underpotential
2
Error: Undervoltage (DC-link circuit). Occurs, if DC-link voltage falls
below the permissible value. Causes:
input voltage too low or unstable
inverter rating too small
voltage losses through wrong cabling
the supply voltage through generator / transformer breaks down at
very short ramps
at F5-G B housing E.UP is also displayed if no communication takes
place between power circuit and control card.
jump factor (Pn.56) too small
if a digital input was programmed as external error input with error
message E.UP (Pn.65).
E.UPh
Error ! Phase failure
3
One phase of the input voltage is missing (ripple-detection)
Warning Messages
A.buS
Warning ! Watchdog
93
Watchdog for communication between operator - PC or operator
- inverter has responded. The response to this warning can be
programmed.
A.dOH
Warning ! drive overheat
96
The motor temperature has exceeded an adjustable warning level.
The switch off time is started. The response to this warning can be
programmed. This warning can be generated only with a special
power circuit.
A. EF
Warning ! ERROR external
fault
90
This warning is triggered via an external input. The response to this
warning can be programmed.
A.ndOH
no ABN.STOP drive overheat
91
The motor temperature is again below the adjusted warning level.
The switch off time is stopped.
A.nOH
no ABN.STOP overheat pow.
mod.
88
The heat sink temperature is again below the adjusted warning level.
A.nOHI
no ABN.STOP overheat
internal
92
The temperature in the interior of the inverter is again below the
warning threshold.
A.nOL
no ABN.STOP overload
98
Warning: no more overload, OL counter has reached 0 %, warning
„overload" can be reset.
A.nOL2
no ABN.STOP overload 2
101
The cooling time after “Warning! Overload during standstill" has
elapsed. The warning message can be reset.
A. OH
Warning ! overheat pow.mod.
89
This warning is output when the defined level is exceeded. Furthermore
the response to this warning can be programmed.
A.OH2
Warning ! motor protection
97
Warning: electronic motor protective relay has tripped. The response
to this warning can be programmed.
A.OHI
Warning ! overheat internal
87
The temperature in the interior of the inverter is above the permissible
level. The switch off time was started. The programmed response to
this warning message is executed.
A. OL
Warning ! overload
99
A level between 0 and 100 % of the load counter can be adjusted.
The warning is output on exceeding this level. The response to this
warning can be programmed.
A.OL2
Warning ! overload 2
100
The warning is output when the standstill continuous current is
exceeded (see technical data and overload characteristics). The
response to this warning can be programmed. The warning message
can only be reset after the cooling time has elapsed and A.nOL2 is
displayed.
further on next side
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...