Page 7.15 - 12
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Special functions
8
256
IA (internal input A)
no
9
512
IB (internal input B)
no
10
1024
IC (internal input C)
no
11
2048
ID (internal input D)
no
Timer display (ru.43 / ru.44)
ru.43 / ru.44 displays the actual counter reading dependent on the adjusted clock source (LE.21 / 26). The
counter can be set to a value by writing on ru.43 / 44. If the clock source is changed during the running time,
the counter content is maintained but is interpreted according to the new clock source.
Timer reset input selection (LE.19 / LE.24)
The inputs which reset the timer can be specified according to the following table. The individual inputs are
OR-operated, i.e. if one of the specified inputs is triggered, the timer jumps back to zero. If a starting and reset
condition are active simultaneously, reset has priority.
(see table "Timer start input selection (LE.17 / LE.22)")
Timer reset condition (LE.20 / LE.25)
According to the following table one can define the conditions to reset the timer additionally to the inputs. The
individual conditions are OR-operated.
LE.20 / LE.25: Timer reset condition
Bit
Decimal value Condition
0
1
Modulation on
1
2
Modulation off
2
4
Actual value = Setpoint value
3
8
Change of parameter set
4
16
Power-On-Reset
Timer display (ru.43 / ru.44)
ru.43 / ru.44 display the actual counter reading depending on the selected clock source (LE.21 / 26). The coun-
ter can be set to a value by writing on ru.43 / 44. If the clock source is changed at run time, the counter reading
remains but is interpreted according to the new clock source.
Comparison level 0...7 (LE.00...LE.07)
LE.00...LE.07 define the level for the switching conditions 37 / 38 ("Timer > Level").
The switching condition is
set if the timer exceeds the adjusted value. A level in the range of -10.737.418,24 to 10.737.418,23 can be
adjusted.But only values of 0...655,35 are sensible for the counter.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...