Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 35
7
Power off controller (not for vector controlled operation with DSM)
There are two controllers: the DC-link voltage controller and the active current controller.
In v/f-characteristic operation the active current controller is subsequently connected to the DC link voltage
controller.
In vector controlled operation, the output of the DC link voltage controller is used as the torque limit.
If the braking torque is selected as the setpoint (Pn.44 bit 6...7 = 3), the DC link voltage controller is deactivated.
Setpoint = start voltage (Pn.44 Bit 6...7 = 0)
The initial voltage value selected with Pn.44 bit 1 is the setpoint of the DC link voltage controller (see also:
tripping of Power-Off
This setting is used to bridge voltage drops. At power recovery, the drive restarts if the output speed is not yet
fallen below the "power off restart level" (Pn.48).
Setpoint = braking torque (Pn.47; Pn.44 Bit 6...7 = 3) (only v/f characteristic operation)
The braking torque can be preset within the range of 0.0...100.0 %.
The braking torque is used as setpoint source, if the drive must be stopped as fast as possible in case of po-
wer failure. The DC link voltage controller is switched off in this case. Since the DC link voltage increases very
strongly in this mode, a braking module is required.
Since the hardware current limit should not be reached with active current control, the setpoint value is limited
internally which can lead to oscillations. In that case the setpoint value can be reduced, which leads to prolon-
gation of the delay. If the voltage stabilization is switched on (Pn.44 bit 8 = "1") and uF.09 = rated voltage is
adjusted, the voltage is not very high and the deceleration is more evenly.
Setpoint = voltage setpoint (Pn.50; Pn.44 Bit 6...7 = 1 or 2) (only v/f characteristic operation)
The setpoint DC-link voltage can be preset in the range of 200...1200 V. The internal value is limited down in
order to ensure a safe operation. The value of the DC-link voltage in normal operation plus approx. 50V adjusts
itself as minimum value. If a braking resistor is connected, the adjusted value may not lie above the threshold
of the braking resistor, else the controller cannot work (threshold 200V-class: 380V; 400V-class: 740V; 600V-
class: 1140V).
If Pn.44 Bit 6...7 = 1, the voltage setpoint is used as setpoint immediately after the triggering of power off. A
restart is only possible in this mode after reaching the standstill.
In mode Pn.44 Bit 6...7 = 2, initial voltage is adjusted to first after triggering. On undershooting the restart value
(Pn.48), the setpoint is increased to the voltage setpoint (Pn.50) with a ramp. This ensures that the drive upon
reaching the standstill in critical applications has enough energy for braking.
KP DC link voltage controller (Pn.51), KI DC link voltage controller (Pn.57),
To be able to adapt the drive individually to the application, the proportional factor of the DC link voltage con-
troller can be adjusted with Pn.51 and the integral factor with Pn.57, in the range of 0...32767. In most cases
the default setting will achieve sufficient results.
If, however, overshoots or fall backs of the motor occur, the
values must be lowered.
KP (Pn.53), KI (Pn.54), KD (Pn.55) (only V/F characteristic operation)
Pn.53, Pn.54 and Pn.55 are the controller parameters of the active current controller
A D-part usually has a positive effect in the control. Pn.55 should have about 10-times the value of Pn.53.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...