Page 7.13 - 34
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Protective functions
400V class = 240V DC; 600V class = 360V DC)
Auto starting voltage (Pn.46)
The auto starting voltage is adjusted with Pn.46 in a range of 50...90% (Default: 80 %) of the rated DC link
voltage (ru.68).
The rated DC link voltage is measured at „Power on“ and displayed in ru.68.
Picture 7.13.10.a Starting the Power-Off function
+
-
ru.68 rated DC voltage
DC-link voltage real value
Auto-DC-link voltage
set value measured at
Power-On
Pn.45 starting voltage
200...1200 V
Pn.46 Auto starting
voltage
50...90% (80%)
Pn.44 Bit 1 starting voltage
0: auto determination of the start
voltage
2: preset the start voltage with
Pn.45
Start of power off if UZK-
actual value < start. volt.
Initial jump for generator operation (only v/f-characteristic operation)
After triggering power off first of all the drive must be brought into regenerative operation that energy can be
regenerated into the DC link. This is achieved by making a frequency jump, so that the speed of the drive is
larger than the output rotating field speed of the inverter.
Figure 7.13.10.b Initial jump for generator operation in 1. cycle
Pn.56 jump factor
0...800 %
Frequency jump
Motor data
Utilisation
Channel 1
Channel 2
Slip calculation
Slip calculation by the active
current
cS.01 actual source
0: Encoder channel 1
1: Encoder channel 2
2: calculated actual
value
Pn.44 bit 2
Starting jump
0: Active current I
W
4: Utilisation I
S
Initial jump calculation (Pn.44 Bit 2)
The parameter Pn.44 bit 2 determines, whether the starting jump is calculated from the active current or from
the utilisation. This setting has no effect on slip regulation. Default value is the calculation of the active current
and it may come to wrong values at high harmonic content of the output current. The initial jump must be deter-
mined from the load in this case. To get proper values enter motor data into dr-parameters first.
Jump factor (Pn.56)
By means of the jump factor the automatically determined starting jump can be adapted to the respective ap-
plication.
In case the jump factor is too small, the inverter trips to "2 Error! Undervoltage" (E.UP)!
For too great a jump factor, the inverter runs into the hardware current limitation (status value 80 "HCL"). The
control cannot work correctly, thus causing a wrong calculation of the active current!
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...