Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 31
7
Motorstrom / Dauerstrom
( Is / Id )
Auslösezeit
dr.34
Motorschutzzeit
min Is/Id
dr.35
Motorschutzzeit
bei Imax
dr.50
Motorschutz
min Is/Id
dr.33
Dauerstrom
A warning level can be adjusted in Pn.15 "OH2 warning level". If the counter reaches this level, the adjusted
response in Pn.14 "Waning OH2 stop. mode" is carried out.
The counter is reduced if the ratio apparent current to continuous current is lower than dr.50. The recovery time
dr.36 "mot.prot. recovery time" is the time the counter requires to count from 100% to 0% (after triggering of
the error, i.e., without current flow). The error triggered by the motor protection function can already be reset
before the recovery time expires.
7.13.10
Power-off function
The Power-Off function has to provide a controlled deceleration of the drive until standstill in case of undervol-
tage (e.g. due to power failure). The kinetic energy of the rotating drive is used to support the inverter DC-link
voltage. As a result the inverter remains in operation and can decelerate the drive in a controlled manner.
Especially in the case of parallel running drives (e.g.textile machines) the uncontrolled running down of the
motors and the consequences resulting from it (thread breakage) can be avoided.
For the various operating modes, the amount of available functions differs.
For the vector controlled modes, some parameters have no function or are even hidden.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...