Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 15
7
For asynchronous motors, the maximum cutoff torque for abnormal stopping can also be increased to make
more torque available for braking, even in the field weakening range.
Pn.67: Quick stop maximum torque corner speed
Value
Explanation
0...32000.00Nm
the limiting characteristic for abnormal stopping is defined by
Pn.67 instead of dr.16.
Quick stop at open loop systems
For abnormal stopping with v/f-characteristic control, the drive is decelerated with the adjusted ramp time, and
at the torque limit, respectively. Whether braking occurs at the ramp or at the current limit is defined in para
-
meter Pn.58.
If no abnormal stopping shall be executed, there are different possibililties for the response, depending on the
type of malfunction.
Additionally, for most malfunctions, issuing the value 6 = warning via a digital output is possible.
Thereby, the inverter does not automatically execute an abnormal stopping. With the warning via a digital out-
put, however, an external control is given the opportunity to respond to the malfunction as is appropriate for
the application. To issue the warning message, a digital output must be programmed with the corresponding
switching condition (see chapter 7.3 Programming of the digital outputs).
Pn.58: Quick stop mode
Bit
Meaning
Value
Explanation
0
Quick stop mode (F5-G)
0: Ramp generator
Abnormal stopping at the abnormal stopping
ramp
1: Differential con-
troller
Deceleration time for abnormal stopping is deter-
mined by means of a controller
1
Quick stop act. value (F5-G)
0: Apparent current
Current limit for deceleration refers to the appa-
rent current
2: Active current
Current limit for deceleration refers to the active
current
2
Abnormal stopping via con-
trol word (SY.50)
0: Sy.50 modulation
off
Shutoff of the modulation after reaching of speed
0 due to abnormal stopping
4: Sy.50 modulation
on
Fast stop with holding torque on reaching speed
0
3
Status bit at standstill
0: Status bit on
The status bit "abnormal stopping" remains
active until leaving the function
8: Status bit off
The status bit "abnormal stopping" is reset when
the drive has reached standstill
For abnormal stopping at the ramp generator, parameter Pn.60 is the ramp time for the deceleration ramp.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...