Page 7.13 - 12
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Protective functions
Error message: "Error! Output phase“ (E.iPH)
Pn.74 Out phase check mode
Value range: 0 (off) .. 1 (on), default value: 0 (off), not set-programmable
Function:
The function is active if all following conditions are met:
Pn.74 = 1 (on)
F5-G or F5-M vvc (cs.00 Bit 0-2 = 0..2)
Output frequency ru.03 > 4 Hz
Utilization ru.13 > Utilization lower limit
Since checking of the phase currents is done with a constant ADC level, the result of the utilization lower limit
is dependent on the value of the overload characteristic:
HRS / OC
Utilization lower limit
125 / 150 %
4.8 %
150 / 180 %
5.7 %
180 / 216 %
6.9 %
200 / 240 %
7.6 %
The release time sets itself load and frequency-dependent between 250 and approx. 400 ms. The cause there-
fore is the strong fluctuating load after disconnecting a phase. The load can fall temporary below the utilization
lower limit, whereby the release time is extended.
7.13.2
Response to malfunction messages
7.13.2.1
Selection of the response
Abnormal stopping (i.e., automatic shutdown of the drive) is possible for all errors that do not enforce immediate
shutdown of the modulation or for which pre-warnings can be generated.
If abnormal stopping is not sensible in the application, the possibility to set a digital output is available for many
malfunctions.
The response is programmable for the following malfunctions:
-
Ext. error
Pn.03
Reaction to external fault
-
Watchdog
Pn.05
Watchdog response
-
Hardware limit switch
Pn.07
proh. rot. stopping mode
-
Set selection error
Pn.18
E.Set stopping mode
-
Software limit switch
Pn.66
Response software limit switch
-
Speed controller limit
Pn.75
Response to error E.SCL
-
Acceleration monitoring
Pn.81
Acceleration error response
Other errors switch off the modulation, but a pre-warnings can be generated prior to their triggering. In the time
between the pre-warning signal and the triggering of the error, the drive can be hut down via abnormal stopping.
The response is programmable:
-
overload
Pn.08
warning OL stop. mode
-
Heat sink overtemperature
Pn.10
Heat sink overtemperature response
-
internal overtemperature
Pn.16
Internal overtemperature response
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...