Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 11
7
7.13.1.13 Speed limit exceeded
The status "58: ERROR! Overspeed“ (E.OS) is triggered, if ru.07 "actual value display" exceeds either the va-
lue of oP.40 / oP.41 "max. output val." or the value of ru.79 „abs. speed EMC“ (only for synchronous motors).
With oP.40 / oP.
41, the user defines limits that may not be exceeded by the application under any circum
-
stances.
ru.79 shows the maximum speed for a synchronous motor which, if exceeded, leads to an EMC of the motor
high enough to damage the DC-intermediate circuit of the inverter.
Reason for the occurence of excessive speed can be too small a distance between the maximum setpoint and
the speed limit, so that overshoots can trigger the error. Other causes can be (e.g., caused by EMC) malfunc-
tions in the speed measurement or a noisy, insufficiently smoothed speed estimate in the encoderless control
(SCL or ASCL).
7.13.1.14 Speed controller limit reached
Pn.75 "response to error E.SCL" determines how the output should respond if the speed controller reaches the
limit, i.e., if the set torque reaches the maximum possible value. In the factory setting, this operating condition
can be applied to a digital output (switching condition "53: Speed control at the limit"). With Pn.75, however, it is
also possible to execute an abnormal stopping on reaching the torque limit (Status "107: ABN. Speed controller
limit"/ A.SCL) or to trigger an error (Status "25: ERROR! speed controller limit“ / E.SCL)
7.13.1.15 Maximum acceleration exceeded
The maximum permissible acceleration is defined with Pn.79 "Acceleration limit 1/s^2".
Pn.80 "Acceleration scan time" determines the time period used for acceleration averaging.
The change of the actual speed (ru.07) in this time period, divided by the scan time (Pn.80) is the actual acce-
leration. The speed difference must be converted from 1/min to 1/s for the calculation of the acceleration.
Speed change during scan time
—————————————————————
60 x acceleration scan time (in seconds)
Acceleration =
If the acceleration exceeds the limit (Pn.79), the response defined by Pn.81 "warning acc. stop mode"
is trig-
gered.
The drive, dependent on the programming, enters the status "24: ERROR! Maximum acceleration" (E.Acc) or
"106: ABN. Maximum acceleration" (A.Acc)
7.13.1.16 General power circuit error
Monitors for the internal hardware (e.g. fans) are integrated on some inverter types. If one of these monitoring
circuits reports an error, "12: general power circuit error" (E. PU) is triggered.
7.13.1.17 Phase loss
"Error! Phase loss" (E. UPh) is identified indirectly via the ripples in the DC link voltage.
If one power phase is missing, the waviness in the DC link is considerably increased under load. In no-load
operation or at small load, the error of the power phase is, however, not recognised. For this error, an automatic
restart cannot be programmed.
Phase loss detection at the output
If one of the output phases is interrupted during operation, this should be detected by the inverter.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...