Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 7
7
7.13.1.5
Inverter over temperature
Heat sink overtemperature
The heat sink temperature acquisition protects the power module from thermal overload. The temperature at
which the inverter switches off with error message "8: ERROR! Overtemperature" (E.OH) depends on the po-
wer circuit (generally 90°C).
After cooling period the status changes from "Error! Overtemperature" to "36: Heat sink temperature normal
again" (E.nOH) and is therefore resettable.
A level between 0° C and 90 °C, when the pre-warning is triggered can be adjusted with Pn.11 "OH warning
level". The response to the warning message is set with Pn.10 "warning OH stop. mode".
Internal overtemperature
The interior temperature monitoring protects the inverter against malfunctions caused by too high temperature
in the interior of the inverter. Upon exceeding a unit-specific temperature the interior fan is activated. If the tem
-
perature is still too high after about 10 min., the disconnecting time set with Pn.17 "internal overtemperature
disconnecting time" (0...120s) starts.
With the start of the disconnecting time, switching condition "11: Warning internal overheating" is met and the
response to the warning message set in Pn.16 "warning OHI stop. mode" is executed.
After expiration of the disconnecting time, "6: ERROR! Overtemperature interior" (E.OHI) is triggered.
When the interior temperature has dropped again, the inverter state changes again to "7: interior temperature
back to normal" (E.nOHI). The error can now be reset.
7.13.1.6
External fault
With Pn.04 "Input selection external error", one or more digital inputs can be programmed which can trigger the
error "31: ERROR! External input" (E.EF).
With Pn.03 "Response to external error"
, the response of the inverter to the digital input is defined. With
Pn.65/
bit 1 "2:Pn.04 = E.UP", the function of Pn.04 can be changed and the triggering of an error via a digital input
can be deactivated.
7.13.1.7
Bus error
The inverter contains two watchdogs that monitor the communication between an external bus, operator, and
inverter control.
With parameter
Pn.05 "Response to E.bus", the response to a watchdog error is defined. Dependent on the
chosen adjustment, either "Error! Watchdog" (E.buS) or "Warning! Watchdog error" (A.buS), is issued or a war-
ning message via a digital output is generated.
Watchdog time (Pn.06)
This watchdog monitors the communication at the operator interface. With activated watchdog, the response
set in Pn.05 is triggered after expiration of an adjustable time (0.01...40 s) without incoming telegrams.
The function is deactivated by setting the value "0: off".
HSP5 Watchdog time (SY.09)
The HSP5 watchdog function monitors the communication of the HSP5 interface (control card - operator; or
control card - PC). After expiration of an adjustable time (0.01...10 s) without incoming telegrams, the response
adjusted in Pn.05 is triggered. Value „0: off“ deactivates the function.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...