Page 7.12 - 64
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Posi- and synchronous operating
PS.40 "reference point window" = 300 increments
The initiator signal is evaluated only if the direction of rotation is counter clockwise and the actual position lies
within a range of700...1300 increments. With this, the reference marker 2 is masked for the return path.
The following figure illustrates the connection between direction of rotation, target, the values
of PS.46 / 47 and
the reference point window PS.40.
GB
4000
5000
6000
7000
M
GA
M
M
M
GA
GB
GB
forward
reverse
Target A
Target B
Reference marker
(300 increments)
Validity range for the
respective target at
clockwise rotation
Validity range for the
respective target at
counter clockwise
rotation
Index A:
PS.24 = 4000
PS.46 = 500
PS.47 = 500
Index B:
PS.24 = 6000
PS.46 = 650
PS.47 = 800
The parameter PS.45 "adjustment index selection" is identical to parameter PS.23 "index/selection". It has
been inserted here a second time only to simplify the operation.
7.12.4.14 Posi mode / start positioning
A "start positioning" command can be generated by various means:
●
via digital input
The digital input is selected via parameter PS.29 "start positioning input selection". Alternatively, the
function "start positioning" can be associated with an input in the parameters di.11...di.22 (see chapter
7.3 Digital inputs)
●
by means of the control word SY.50 or SY.43
To start the positioning by means of the control word Sy.43 ("control word long") and Sy.50 ("control
word low"), respectively, bit 10 "start positioning" must be switched from 0 to 1.
Sy.43: Control word long
Sy.50: Control word low
Bit
Meaning
Value
Explanation
10
Start positio-
ning
0
Without function for positioning
1024
Switch from not activated to activated starts positioning
Starting a new positioning is only possible if bit 10 has temporarily been set to 0.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...