
Torque display and -limiting
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.8 - 11
7
of the characteristic to lower speeds.
For value 4 ("on" ), the limiting characteristic is shifted in both directions, to lower speeds at lower voltage, and
to higher speeds at higher voltages.
At this value, the motor achieves maximum torque. It is unfavorable especially at regenerative operation that
the DC link voltage can increase very quickly and in a wide range. These dynamic changes can cause high
disturbance in the field weakening range.
Therefore preferable setting is 8 („>Un(FI) = off, abnormal stopping = off“). Only the necessary physical shifting
of the characteristic due to low DC link voltage is executed here.
That means the characteristic is only shifted if the DC link voltage is lower than the rated DC link voltage (= √
2 * inverter rated voltage).
There is no shifting if the DC link voltage is higher than the rated voltage.
Value 12 („>Un(FI)= off, abnormal stopping= on“) can be selected if the maximum achievable torque shall
be available for emergency stop. In this mode the characteristic at higher DC link voltage is shifted to higher
speeds only during emergency stop operation. Generally value "8" should be used if possible.
7.8.3.2.4
Influence of the current limit
The total power of the motor in the field weakening range consists of active current and magnetizing current.
The maximum torque limits only the active current.
For some motors there is a maximum current specified in the data sheet. This is valid for both components
together. Therefore the total motor current can be limited by this parameter.
The magnetization current has priority if both components together exceed the current limit.
Attention:
To ensure that the speed controller can control the drive, active current flow must always be able. Therefore the
magnetizing current limit (dS.13) must be significant
lower than the maximum current (dr.37). Maximum dS.13
should be 0.75 x dr.37.
The max. current limit dr.37 is activated via bit 0 of parameter dS.03.
dS.03: Current-/torque mode
Bit
Meaning
Value
Explanation
0
max. current-/ torque
mode
0: off
software-based current limit off
1: on
software-based current limit on
7.8.3.3
Additionally torque limiting in the field weakening range
Addr.
Parameter
Name
Default value
Value
1103h
dS.03
Isq limit, Ds.37
off
0 = off
128 = on
1125h
dS.37
usd max modulation ref.
95%
0 ... 100 %
A possibility to limit the maximum torque in the field weakening is via the characteristic dr.39 .. dr47
and the ad-
justments in ds.03 bit1..3. This has the disadvantage that the characteristic must be determined, either abstract
calculated with the "known motor data" or measured at the test stand. Also the consideration of the DC link
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...