Speed control
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.7 - 3
7
7.7
Speed control
The speed controller is a PI controller.
A PT1 low pass filter is series-connected.
The integral factor Ki can be changed speed-dependent. The proportional factor Kp can be increased propor-
tionally to the control deviation.
In order to improve the control performance of the drive (low overshoot, higher dynamics), the speed controller
can be pre-controlled with known mass-moment of inertia.
7.7.1.
Speed controller parameters
7.7.1.1
Initial setting
The speed controller is a PI controller.
The proportional factor "Kp speed" is adjusted in cS.06 and the integral factor "KI speed" in cS.09
7.7.1.2
Automatic adjustment of the speed controller (only at operating with motor model)
Kp (cS.06) and Ki (cS.09) of the speed controller can be preset by the inverter. For this the mass-moment of
inertia of the complete system (motor + rigidly coupled load) must be entered in cS.25 „inertia“.
After the input of the motor data once parameter
Fr.10 "Reset field-oriented control parameter" = 1 or 2 must
be written. Thus dependent on the adjusted rated power (dr.03) the mass-moment of inertia was pre-charged
for a standard asynchronous motor in cS.25. The value of cS.25 has the right dimension for 50Hz standard
motors, because at some applications the ratio of the load inertia is in a range of 0.5...2 x motor inertia.
Better results can be realized if the total moment of inertia is exactly preset. If the value is unknown it can be
determined.as described in chapter 7.7.2.
Parameter cS.26 „optimisation" determines the control characteristic which should be achieved by the calcu-
lated parameters.
Parameters for a dynamic, hard speed controller adjustment are calculated with cS.26 = 2. Interference fac-
tors, such as torsion or tolerance of the load coupling can intensify vibrations, so that a higher value must be
entered in cS.26.
Parameters for a very soft and slow speed controller adjustment are calculated with cS.26 = 15. Which value
between 2 and 15 is most suitable for the application is depending on the oscillation-grade of the total system.
An oscillation of the estimated speed is a possible disturbance at encoderless operation of asynchronous mo-
tors (ASCL). Extension of parameter "ASCL speed PT1 time" (ds.17) often enables a dynamic speed controller
adjustment, i.e. a smaller value for cS.26.
The precharging of the speed controller parameters can be deactivated with the adjustment of value "19 = off"
in cS.26.
The speed controller parameters are overwritten when the value for cS.26 is changed.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...