
Page 7.5 - 28
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Motor data and controller adjustments of the asynchronous motor
7.5.2.4.1
ASCL / low speed operation
The operation at small speed is a critical range which should be passed very quickly.
The size of this range cannot be indicated universally valid. It is strongly dependent on the used motors.
The usable speed range for standard-asynchronous motors is approx.:
Power
mot. opera-
tion
gen. opera-
tion
2.2 kW
1 : 50
1 : 20
85 kW
1 : 100
1 : 50
Start-/ stop ramp for low speed (dS.21 / dS.22)
In order to leave the critical range of small speed at starting and stopping there is an additional ramp for this
range.
The ramps is defined by parameter dS.21 "auxilliary ramp/ speed limit" and dS.22 "auxilliary ramp/
time".
Parameter dS.21 indicates the speed range for which the start ramp applies. dS.22 indicates the acceleration-/
deceleration time.
200 min
-1
Anzeige Rampenausgang
( ru.02 )
Zeit
0,2 s
Example:
ud.02 = 4 (4000 rpm mode)
dS.21 = 200 rpm
dS.22 = 1s
ASCL model shutoff during deceleration (dS.19, dS.20)
If the drive is to be stopped, the critical range of low frequencies must be passed again.
The additional problem of the drive not stopping completely, but instead running permanently at a low frequency
with a very high current occurs here, leading to a miscalculation of the speed.
Under the following conditions, therefore, the mode is switched from vector controlled to current regulated,
frequency controlled operation:
- Drive decelerates
- the
estimated output frequency is smaller than dS.19 ("speed limit model switch-off DEC")
The drive then shows the following behaviour:
- the
output frequency is ramped down according to the adjusted deceleration ramp
- the
current is kept constant starting from the switching time
The parameter dS.19 is loaded with a default
value by the identification or by Fr.10 "reset field-oriented control
-
ler parameters". Should problems still occur during deceleration, the value for dS.19 can be increased.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...