Motor data and controller adjustments of the asynchronous motor
motor data sheet for dr.08.
Due to saturation, parameter dr.10 "TPIM main inductivity" depends on the chosen magnetising current. This
is
defined by the
rated motor current (dr.00), cos(phi) (
dr.04) and factor flux adaption (
dr.19). Since the value of
the main inductance given in the motor data sheet possibly applies for a different current, this parameter (dr.10)
must
always be identified, to ascertain the correct
value of the current magnetising current.
7.5.2.3.1.1
Identification /
general
The required equivalent circuit data for the motor model can be determined by the KEB COMBIVERT itself.
First the motor data must be entered and the motor adaption must be executed according to chapters 7.6.1.
There are two possibilities to start the
identification:
-
Writing of parameter dr.48 in inverter state "stop (mod. off)", measurement is starting auto-
matically.
-
Writing of parameter dr.48 in inverter state "nop" with subsequent control release.
Parameter dr.48 cannot be written in other operating conditions.
The measured values can be invalid in case of strong overdimensioning of the inverter. The rated current of the
motor should be at least 1/3 of the maximum short time current limit. The short time current limit is determined
by the overload characteristics and can be taken from the power circuit manual or parameter In.18 (hardware
current).
The direction of rotation during identification of the main inductance is always "clockwise rotation"!
Value „82: calculate drive data / Cdd“ is output in inverter state ru.00 during the measurement. After success-
ful measurement the display is ru.00 = „127: drive data calculated / Cddr“.
If the measurement is interrupted with an error, ru.00 = 60 ERROR! drive data/ E.Cdd" is displayed.
No correct operation can be ensured in case of interruption.
The actual state of
the identification is
displayed in parameter dr.62 "state motor ident." The control release
must be switched off in order to leave the identification mode.
Parameter dr.48 must be written again in order to start a new measurement.
If the internal brake handling is used in the application, then it must be deactivated for the
identification. For
safety reasons the output signal "brake release" is not set during measurement, since the motor cannot gene-
rate a defined torque in this
time. Stator resistance, rotor resistance and leakage inductance can be measured
also at engaged brake.
For the
identification of the
main inductance, the drive must be decoupled from the load and the output swit-
ching condition which is assigned to the break control must be set to value "1" (= always active), setting the
brake permanently open.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...