Motor data and controller adjustments of the asynchronous motor
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.5 - 9
7
Adhere to the following procedure:
-
Enter motor data of the type plate into the parameter set which is to program
-
possibly call and activate parameter set
-
Execute the measurement dependent on the operational case in cold status respectively let the motor
warm up to operating temperature.
-
Preset no direction of rotation (inverter must be in status "LS")
-
Activate control release
-
maximum value "250000" of parameter dr.06 starts the resistance measurement
During the determination the status display (ru.00) indicates "Cdd". Upon successful determination the motor
stator resistance is entered in dr.06. If an error occurs during determination then error signal "E.Cdd" is output.
7.5.1.7.3
Load motor dependent para. (Fr.10), controller activation
After input of the rating plate data of a new motor or after automatic measurement of the stator resistance, an
automatic optimisation of the torque and slip compensation can be carried out with Fr.10 (see chapter 7.5.1.7).
The optimisation is started by writing value "3" on Fr.10. Thereby the inverter must be in status „noP“ (no control
release). Provided that only one motor is used, the measurement can occur with direct set programming for all
parameters at once.
Fr.10: Load motor dependent parameter
Value
Function
Description
0
finished
loading completed
1
uF.09
only for closed loop operation
2
act. DC link voltage
only for closed loop operation
3
SMM
Adjustment for torque and slip compensation
Following parameters are changed by the activation of Fr.10:
-
uF.00 rated frequency = Motor rated frequency (dr.05)
-
uF.01 boost = calculated value
-
uF.02 additional point of support (frequency) = -0,0125 Hz (parabolic characteristic)
-
uF.02 additional point of support (voltages) = 0,0%
-
uF.09 voltage stabilisation = rated motor voltage (dr.02)
-
uF.16
torque compensation / configuration = 1 (sign-sensitive)
-
uF.17
torque compensation / amplification = 1,2 (Default
value)
-
cS.00 controller configuration = 34 (speed control SMM + breakdown slip limit (
dr.09))
-
cS.01 actual source = 2 (calculated)
-
cS.04 speed control limit = 4 • nominal slip of the motor
-
cS.06 KP speed controller = 50
-
cS.09 KI speed controller = 500
The adaption covers
approx. 90 % of the applications. For an application-specific adjustment a manual fine
adjustment can now still be carried out for an individual case.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...