Motor data and controller adjustments of the asynchronous motor
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.5 - 7
7
7.5.1.5 Switching frequency (uF.11)
Information on the carrier frequencies can be found in chapter 7.10.3 "Carrier frequencies and Derating".
7.5.1.6 Energy saving function (uF.06...08)
The energy saving function allows the lowering or raising of the current output voltage. Corresponding to the
activation conditions defined in uF.06, the voltage
corresponding to the V/f characteristic is scaled by the energy
saving factor (uF.07).
If torque compensation is active (s. chapter 7.5.1.7), the energy saving function is used for control optimization.
The V/f characteristic will then not be affected.
The maximum output voltage cannot be higher than the input voltage, even for a factor > 100 %.
The function is used for example in cyclic executed load/no-load applications. During the no-load phase the
speed is maintained, but energy is saved as a result of the voltage reduction.
uF.07 Energy saving factor
0.0…130.0 % (default 70 %)
uF.08 Energy saving input selection
0...4095 (Default 0)
For the assignment of the inputs to the parameter values, refer to chapter 7.3.1 "digital inputs".
uF.06 Energy saving mode
Bit
Description
Value
Function
0...3
Activation
0
generally off
1
generally active
2
at actual value = setpoint
3
via digital input
4
at clockwise rotation
5
at counter clockwise rotation
6
at constant run clockwise
7
at constant run counter-clockwise
8...15
generally off
4...7
Voltage ramp
0
Standard time *
16
time / 2
32
time / 4
48
time / 8
64
time / 16
* default setting 1.6s
7.5.1.7 SMM (sensorless motor management)
The SMM-function (sensorless motor management) includes the torque and slip compensation. These two
functions can be activated separately. For an optimal control characteristic, the combination of both functions
is required.
Setting the correct motor data is required, since they are used in calculations needed by the inverter to achieve
the best possible results in the control of boost and slip.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...