Digital in- and outputs
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.3 - 39
7
With parameters do.08...do.15 each of the 8 switching conditions (do.00...do.07) can be inverted separately
for each flag.
With this function it is possible to set any chosen switching condition as non-condition. The pa-
rameter is bit-coded. According to Fig. 7.3.15 theweighting for the switching conditions to be inverted must be
entered in do.08...do.15. If several conditions shall be inverted, the sum is to be formed.
Example:
Output X2A.19 shall be set when the inverter is not accelerating! In this case we assign the switching condition
21 (inverter accelerates) for example to do.01 (enter value 21). We invert the switching condition (do.01) with
do.09, so enter value „2“.
7.3.19 Selection of switching conditions for flags 0...7 (do.16...do.23)
Parameters do.16...do.23 serve for the selection of the 8 preassigned switching conditions. The selection is
done foreach
flag separately, where one can choose between no one and up to all 8 switching conditions.
The
value of the selected switching condition must be entered in do.16...do.23 in accordance with fig.
7.3.15 . If
several conditions shall be inverted, the sum is to be formed.
7.3.20 AND/OR connections of the switching conditions (do.24)
After the switching conditons are selected for each output, it can now be determined, how these are connected.
As a default all conditions are OR connected, i.e. the flag is set if one of the selected conditions is fulfilled.
Another possibility is the AND connection which can be adjusted with do.24. AND connection means that all
selected conditions must be fulfilled before the flag is set.
Parameter do.24 is bit-coded. The table under 7.3.17 shows the assignment.
Fig. 7.3.20 Linking the switching conditions in logic step 1
&
>1
0
1 Bit 0
8
do.16
&
>1
0
1 Bit 1
8
do.17
&
>1
0
1 Bit 7
8
do.23
do.24
Flag 0
Flag 1
Flag 7
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...