Digital in- and outputs
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.3 - 33
7
7.3.17 Switching Conditions (do.00...do.07)
From the following switching conditions one can select up to 8 for further processing. The values are then
entered in the parameters do.00...do.07.
do.00...do.07: Switching conditions
V a -
lue
Function
Description
0
always switched-off
Switching condition never fulfilled
1
Always active
Switching condition always fulfilled
2
Run signal
Drive is running and there is no malfunction (also set if modulation generally
released, but temporary blocked by for example "motor de-excitation").
3
Ready for operation
Drive is ready for operation (inverter state unequal to error).
4
Error
There is an error message (inverter state equal to error).
5
Error without auto reset
Is not set for errors for which an automatic restart is programmed.
7
Alert signal overload
ru.39 is an overload counter, counting in steps of 1%. On reaching 100 % the
inverter switches off. Upon exceeding of level Pn.09 (default 80 %) the over-
load warning is given. The performance in case of a warning can be adjusted
with Pn.08 (response to OL-warning).
8
Pre-warning power modules
overheating
Overheating-prewarning (OH)! Depending on the power circuit the inverter
switches off between 60...95°C heat sink temperature. The prewarning is
output, when the level OH-warning (Pn.11) is reached (default 70 °C). The
behaviour in case of an warning can be adjusted with Pn.10 (response to
OH-warning).
9
Pre-warning motor overheating
PTC-prewarning (dOH), on tripping of the motor-PTC connected to the termi-
nals T1/T2. After expiration of an adjustable switch-off time Pn.13 (0...120s)
the inverter switches off with E.dOH. The behaviour in case of a warning can
be adjusted with Pn.12 (response to dOH-warning).
10
Motor protection relay function
F5-M and F5-H (asynchronous motors):
The defined motor protection release time according VDE is up. The beha
-
viour on the release of the electronic motor protection relay can be adjusted
with Pn.14 (warning OH2 stop. mode).
F5-S and F5-E (synchronous motors):
The overload counter of the motor protection function for servo motors has
exceeded the value of Pn.15 „OH2 warning level“. If the counter reaches
100%, the error is released. The response to this pre-warning can be adju-
sted with Pn.14 (warning OH2 stop. mode).
11
Warning internal overheating
Interior temperature-prewarning (OHI) is output if the interior temperature of
the inverter exceeds the level OHI-warning. The behaviour can be adjusted
with Pn.16 Pn.16 (response to OHI-warning). An error is generally released
after expiration of the OHI-delay time (Pn.17). Not at Pn.16 = „7“
12
Cable breakage 4...20mA AN1
Cable breakage at 4...20mA setpoint setting at An.01 or An.02. Trips, if the
setpoint current drops below 2mA.
13
Cable breakage 4...20mA AN2
14
Current limit ( I > Pn.20 )
Pn.20 „current limit level“ exceeded (only for v/f characteristic open-loop
operation).
15
Ramp stop active
Ramp is stopped (LA-/LD-Stop active). Pn.24 „LAD load level“ or Pn.25 „LD
voltage“ exceeded at acceleration/deceleration.
16
DC-braking active
DC braking active
17
Power off function active
The state of the inverter is „Power off function active“.
further on next side
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...