Page 7.3 - 32
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Digital in- and outputs
Description
For the switching of the digital outputs one can choose up to 8 conditions from the 91 different conditions.
These are entered in do.00...do.07. Switching condition 0 and 1 can be filtered by do.43 and do.44. Parameter
ru.23 displays, if one or several of these conditions are met
. For each flag it can now be selected which
of the 8
conditions shall apply to it (do.16...do.23). Each condition can still be inverted before selection (do.08...do.15).
As a standard all conditions (if several are selected) are OR operated. With do.24 this can be changed to AND-
operation .
i.e. all conditions selected for this flag must be fulfilled before it is set. Parameter ru.24 displays the
flags which are set in this stage. do.33...40 form a second logic step where a selection of the flags from
logic
step 1 can be made.
Each individual flag can be inverted with do.25...32. do.41 adjusts the type of the linkage
(AND/OR). Parameter do.42 is used for inverting one or several outputs. With do.51 the output signals are
assigned to the terminals. ru.80 serves for the display of the digital output state, thereafter ru.25. The internal
outputs OA...OD are directly connected with the internal inputs IA...ID.
7.3.15 Output signals / hardware
Fig. 7.3.13a Transistor outputs
Fig. 7.3.13b Relay outputs
The total current of X2A.18,19 is limited to 50mA. In case of inductive load at the relay outputs or at the transi-
stor output a protective wiring is to be provided (free-wheeling diode)!
7.3.16 Output filter (
do.43, do.44)
A filter can be set for switching condition 0 with do.43. For switching condition 1 with do.44. The change of a
switching condition must be applied for
the filter time, then it becomes active at the output of the filter
. If the
change of a switching condition is cancelled during the filter time, the filter time is reset and restarted with the
next change. The filter time can be adjusted in a range of 0 (off)...1000 ms.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...