Page 7.3 - 22
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Digital in- and outputs
7.3.5 Digital
noise filter (di.03), fast digital noise filter (di.23)
The digital
noise filter
reduces the susceptibility to interferences on the digital inputs. Only hardware inputs can
be filtered. Each input has a separate filter counter that counts up at active input and down at inactive input.
The output of the filter is set on reaching the filter time and reset when zero is reached.
Parameter
Setting range
Resolution
di.03
0...127 ms
1 ms
di.23
0...31.75 ms
0.25 ms
Priority of the filter times: The larger of the two times is used.
7.3.6 Inversion of Inputs (di.04)
With parameter di.04 it can be adjusted whether a signal is 1- or 0-active (inverted). The parameter is bit-coded,
i.e. the value corresponding to the input mut be entered. If several inputs shall be inverted, then the sum is to
be formed. (Exception: An inversion of the control release remains without function).
7.3.7 Delay activation / deactivation digital inputs
40
I1 ON delay
di.41
I1 OFF delay
di.42
I2 ON delay
di.43
I2 OFF delay
di.44
I3 ON delay
di.45
I3 OFF delay
di.46
I4 ON delay
di.47
I4 OFF delay
di.48
IA ON delay
di.49
IA OFF delay
di.50
IB ON delay
di.51
IB OFF delay
di.52
IC ON delay
di.53
IC OFF delay
di.54
ID ON delay
di.55
ID OFF delay
Value range: 0 (off) ... 32.00 s; Resolution 0.01s; Default value : 0 (off), not set-programmable
Function:
The function can be switched off with the value di.40 – 55 = 0.
The ON delay starts with the positive edge of the input, the OFF delay with the negative edge.
In the following example I1 and I2 are first switched individually and then simultaneously.
The four required times are different adjusted.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...