KEB COMBIVERT F4-C
Name: Basis
20.03.98
4
CP - Parameter
©
KEB Antriebstechnik, 1997
All Rights reserved
Operation
Chapter
Section
Page
Date
4.3.1 Operation in
CP-Mode
4.3
CP-Parameter
The Customer-Parameters (CP) are a special group of parameter. With the
exception of CP.0 (Password input), they can be defined by the user. The following
Parameters are preset at delivery.
Advantages from it: - operator-friendly for the customer
- critical parameters are protected against maloperation
- low documentation cost for the machine builder
FUNCT
SPEED
▲
START
▼
STOP
▲
START
▼
STOP
Adjustment of
parameter number
Adjustment of
parameter value
Compared to the Application-Mode the operation in the CP-Mode is easier because
parameter set selection and parameter group selection are unnecessary.
The following list shows the CP-parameter group predefined by us. The definition
of the CP-parameters is done in the User-Definition-Parameters (ud). How you can
define your own parameters is described in Chapter 5.
Display
Parameter
Setting Range
Resolution Factory Setting
Source
CP. 0
Password input
0...9999
1
-
ud. 0
CP. 1
Actual frequency display
-
0,1 Hz
-
ru. 3
CP. 2
Status display
-
-
-
ru. 0
CP. 3
Actual load
-
1 %
-
ru. 7
CP. 4
Peak load
-
1 %
-
ru. 8
CP. 5
Rated frequency
0...409,58 Hz
0,0125 Hz
50,0 Hz
0.uF. 0.
CP. 6
Boost
0...25,5 %
0,1 %
2 %
0.uF. 1.
CP. 7
Acceleration time
0,01...300 s
0,01 s
10 s
0.oP.11.
CP. 8
Deceleration time
0,01...300 s
0,01 s
10 s
0.oP.12.
CP. 9
Minimum frequency
0...409,58 Hz
0,0125 Hz
0 Hz
0.oP. 4
CP.10
Maximum frequency
0...409,58 Hz
0,0125 Hz
70 Hz
0.oP. 5.
CP.11
Fixed frequency 1
0...409,58 Hz
0,0125 Hz
5 Hz
0.oP.22.
CP.12
Fixed frequency 2
0...409,58 Hz
0,0125 Hz
50 Hz
0.oP.23.
CP.13
Fixed frequency 3
0...409,58 Hz
0,0125 Hz
70 Hz
0.oP.24.
CP.14
max. ramp current
10...200 %
1 %
140%
0.Pn. 5.
CP.15
max. constant current
10...200 %
1 %
200%
0.Pn.13.
CP.16
Speed search
0...15
1
8
0.Pn. 7.
CP.17
Voltage stabilization
150...649 V,oFF
1 V
off
0.uF. 8.
CP.18
Slip compensation
-2,50...2,50
0,01
0=off
0.cn. 1.
CP.19
Autoboost
-2,50...2,50
0,01
0=off
0.cn. 2.
CP.20
DC-braking
0...9
1
7
0.Pn. 8.
CP.21
DC-braking time
0...100 s
0,01 s
10 s
0.Pn.11.
CP.22
Relay output
0...25
1
2
0.do.2.
CP.23
Frequency level
0...409,58 Hz
0,0125 Hz
4 Hz
0.LE. 2.
CP.24
Setpoint signal
0...2
1
0
An. 6.