22
INSTALLATION AND CONNECTION
4.2.1 Rated data of the integrated fans
Description
Data
Connection terminals
+, -
Rated DC voltage
24 V
Permissible DC voltage range
18 V...27.6 V
Rated current
0H, 0L: 3 x 0.13 A = 0.4 A
0P, 0S: 6 x 0.5 A = 3 A
0X, 0Y: 6 x 1.2 A = 7.2 A
Fuses F1...F3
Flat fuse ATC 32 V Company Bussmann
0H, 0L: ATC1 (1.0 A)
0P, 0S: ATC2 (2.0 A)
0X, 0Y: ATC3 (3.0 A)
Colour code fuse
Grey
Table 8:
Voltage supply of the integrated fans
4.2.2 Overtemperature shutdown
The chokes are equipped with temperature switches in order to protect the system
against inadmissible overtemperatures. These must be interconnected with the input
terminals T1/T2 of the AIC drive converter.Rated data NC contact temperature monitor-
ing.
Description
Data
Tripping temperature
155 °C
AC cos φ = 1.0
2.5 A / 250 V
AC cos φ = 0.6
1.6 A / 250 V
DC ohmic
1.6 A / 24 V
DC ohmic
1.25 A / 48 V
Table 9:
Rated data NC contact