ma_dr_e6-hf-filter-nb-20337731_en
Motor cable length
100 m
Output frequency
5 Hz
Switching frequency
8 kHz
①
②
Fig. 9:
33E6T60-3150 interference voltage measurement C2 8kHz 100m
1 QPeak
2 Average
9.2 Informative values for the use of RCDs
Filter
Switching frequency
drive controller
30 mA
100 mA
300 mA
500 mA
Tripping current
33E6T60-3150
2 kHz 50 m
43 %
26 %
25 %
25 %
2 kHz 100 m
-
36 %
35 %
35 %
4 kHz 50 m
46 %
24 %
24 %
24 %
4 kHz 100 m
-
36 %
36 %
36 %
8 kHz 50 m
39 %
39 %
39 %
39 %
Tab. 7:
Informative values with RCD Doepke 4B SK