KE2 Temp All-In-One Quick Start Manual Download Page 1

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.3.65

June 2019

KE2 Temp 

+ Air Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Condensed Quick Start Guide

Supplies List

The accessories required for the controller to work are supplied. 

However, some truck stock items may be needed. See the following list.

  

conduit to go between the controller & evaporator

  

(2) conduit connectors 

(straight or elbow as required)

   (

4) high voltage wires 

(matched to the load of the liquid line solenoid/

compressor and the controller.)

This reference should remain on site with the installed controller.

Programming

  Press & hold ENTER button 

to access setpoint menu

  Use arrow buttons to 

select function:

tS    =  Temperature Setpoint

diF   =  

CSH  =  Max Compressor 

Starts/ Hour

dPd  =  Defrost Per Day

dFt  =  Defrost Time

LAO =  

tAd  =  Temp Alarm Delay

Adr  =  Mod Bus Address

Unt  =  Units for temp display

  Press ENTER & use arrows 

to change value

  Press & hold ENTER button 

Alarms

  When amber LED is lit:

SSA  =  Shorted Sensor Alarm

OSA  =  Open Sensor Alarm

HtA  =  High Temp Alarm

LtA  =  Low Temp Alarm

pn 20679  

 06/14

B

C

D

E

F

A

G

What’s in the Kit

The following parts are included:

 

(1) KE2 Temp + Air Defrost controller

  (1) temperature sensor - 45”
  (1) sensor ziptie
  (1) liquid tight cord grip
  (4) self-tapping mounting screws
  (2) screws for high voltage shield
  (1) programming sticker

A

C

D

E

B

F

G

Use the  

     

 up and      down arrows to scroll through available setpoints.   

Access Setpoint mode by pressing and holding the             button 

until tS (temperature setpoint) displays on the screen   

ENTER

ENTER

Press              to view the current setting.

tS   =   Temperature Setpoint

diF   =   Differential

CSH   =   Maximum Compressor Starts/Hour

dPd   =   Defrost Per Day

dFt   =   Defrost Time

HAO  =   High Alarm Offset

LAO  =   Low Alarm Offset

tAd   =   Temp Alarm Delay

Adr   =   Mod Bus Address

Unt   =   Units for temp display (FAH or CEL)

Setpoints

Use the        up and      to change the setpoint

ENTER

Press              to move between the digits to accelerate the changes.

ENTER

Press              and hold to confirm each setpoint change

BACK

Press              to escape.

 

Only visible if 

CUS (custom) is 

selected for dPd 

(Defrost per day)

Alarms - 

When amber LED is lit:

SSA =   Shorted Sensor Alarm 

OSA  =   Open Sensor Alarm

HtA  =   High Temp Alarm

LtA   =   Low Temp Alarm 

Indicator 

Lights:

Red  blinking -  Real Time Clock battery needs to be replaced
Yellow light - non-critical alarm (system running)
Green light - compressor on
Green blinking - compressor waiting on timer to start/stop

tOd

 d1

 d2

 d3

 d4

 d5

 d6

 d7

 d8

 d9

 d10

 d11

 d12

  

wire labeling 

(numbers, colors, etc.)

  

additional wire ties

   18 gauge twisted shielded pair 

(if extending sensor wires)

   Cat5e wire 

(if adding communication)

  

foam insulation

 

(if running wires outside the space)

 

 silicone

 

(for sealing any box penetrations)

Controller Navigation

Complete Instructions

Please visit:  http://ke2therm.com/product/ke2-temp-defrost/

and click the Link to Literature button

use this QR code. 

KE2 Temp Literature

— OR —  

   

KE2 Temp Videos

Basic Setpoints

Setpoint  Description

Minimum

Default  Maximum

tS

Temperature Setpoint -50

°

F (-45

°

C)

 

35

°

F

100

°

F (38

°

C)

diF 

Differential

1

°

F (1K)

2

°

F

30

°

F

 

(17K)

CSH  Max. Comp. Starts/Hr. 5 (Off)*

6

10

dPd  Defrost Per Day

0

6

12, CUS**

dFt

Defrost Time

0 min

15 min

720 min

HAO  High Alarm Offset

1

°

F

 

(1K)

5

°

F

10

°

F

 

(6K)

LAO  Low Alarm Offset

1

°

F

 

(1K)

3

°

F

10

°

F

 

(6K)

tAd 

Temp Alarm Delay

1 min

90 min

180 min

Adr 

Mod Bus Address

1

1

247

Unt 

Units for temp display  FAH

FAH

CEL

*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature 

being turned off. The compressor will then function on temperature only.
** Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.

For a complete list of setpoints and descriptions see Q.3.20.