Programming
Press & hold ENTER button
to access setpoint menu
Use arrow buttons to
select function:
tS = Temperature Setpoint
diF =
CSH = Max Compressor
Starts/ Hour
dPd = Defrost Per Day
dFt = Defrost Time
LAO =
tAd = Temp Alarm Delay
Adr = Mod Bus Address
Unt = Units for temp display
Press ENTER & use arrows
to change value
Press & hold ENTER button
Alarms
When amber LED is lit:
SSA = Shorted Sensor Alarm
OSA = Open Sensor Alarm
HtA = High Temp Alarm
LtA = Low Temp Alarm
pn 20679
06/14
© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.3.20 (Q.1.20)
October 2016
KE2 Temp
+ Defrost
(pn 20611)
For
Medium Temperature
Applications with
Air Defrost
Installation Manual
Supplies List
All of the accessories required for the controller to work
are supplied, however, standard truck stock items are re-
quired to install the controller. A list is provided below:
conduit to go between the controller & evaporator
(2) conduit connectors (straight or elbow as required)
(4) high voltage wires matched to the load of the
liquid line solenoid/compressor and the controller.
wire labeling (numbers, colors, etc.)
additional wire ties
18 gauge twisted shielded pair (if extending sensor
wires/adding communication)
foam insulation (if running wires outside the space)
silicone (for sealing any box penetrations)
This reference should remain on site with the installed KE2 Temp + Defrost controller.
What’s in the Kit - Parts List
The following parts are included in the
KE2 Temp + Defrost kit:
(1) KE2 Temp + Defrost controller
(1) temperature sensor - 45”
(4) self-tapping mounting screws
(1) liquid tight cord grip
(1) sensor ziptie
(1) programming sticker
(2) screws for high voltage shield
B
C
D
E
F
Select Mounting Location
The KE2 Temp is designed for a wide range of applications; therefore
there are many potential installation locations. Breaking down the in-
stallation location by application provides the most helpful reference.
Application
Locations
Under counter
Evaporator cabinet
Outside controlled space
Walk-in
Evaporator cabinet
Adjacent to entrance
Side-by-side
Above door
Walk-in
Under Counter
Commercial
Wine Cabinet
A
F
A
C
D
E
B
F
G
Quick & Easy
Remote Communication,
Control & Alarming
when used with
the KE2 LDA
Remote Monitoring, Control, Alarm Notifications
The KE2 Temp includes RS-485 Modbus communications, and can now
be accessed remotely using the KE2 Local Area Dashboard and Alarms
(KE2 LDA). See page 4 for additional details.
Service Call Saver -
Post Defrost Indicator
To eliminate unnecessary service calls, the KE2 Temp + Defrost alerts
the user when it is coming out of a defrost cycle using the onboard
display. The display alternates between dEF and the actual temperature
measured by the air sensor. This continues until the temperature has
reached setpoint, or for the amount of time set by dFt (Defrost Time)
whichever is shorter.