Quick guide Technical parameters
multicount D5-3P-75A-MIDmulticount D5-3P-1/5A-MIDmulticount D5-2-ES-75A-MIDmulticount D5-2-ES-3P-1/5A-MID
MID-Counter
24468_EDEBDA0270-
11
20-1_DE-EN
Page 1: ...Quick guide Technical parameters multicount D5 3P 75A MID multicount D5 3P 1 5A MID multicount D5 2 ES 75A MID multicount D5 2 ES 3P 1 5A MID MID Counter 24468_EDEBDA0270 1120 1_DE EN...
Page 2: ...tion 12 Current transformer 5A und 1A 12 Installation instruction 12 Cable requirement 65A 13 Display Language 13 Configure of display language 13 Bus interface KBR eBus only multicount D5 2 xxx MID 1...
Page 3: ...of information about the product the hand ling of the product or the relevant part of the user manual to which particular attention should be drawn DISCLAIMER The contents of this document have been c...
Page 4: ...necting the device adhere to the information given in the connection diagram see Connection diagram and that the connec ting cables are not live When wiring always ensure that all cables used are neit...
Page 5: ...destroy the current transformer The usual local security and work rules must be observed The installati on of the meter must be carried out by qualified and trained personnel NOTE Der multicount D5 xx...
Page 6: ...L3 For meter with CT s Current Transformer ratio If present remove the short circuit on the current transformer Terminal tightening torque Read out interface Correct address Neutral conductor connect...
Page 7: ...pulse output 0 4 Nm max 2 5mm2 strand Tariff control 0 4 Nm max 2 5mm2 strand Cable requirement 65A Type Wire Cu cross section 35mm Outside 9 55 mm DISPLAY LANGUAGE Display language can be selected be...
Page 8: ...n clamp 5 NE outer cond switched on clamp 3 E3 respectively 4 E4 Double tariff Four tariff optional E4 E4 E3 T1 0 T1 0 0 T2 1 T2 1 0 T3 0 1 T4 1 1 0 no voltage 1 voltage CURRENT TRANSFORMER RATIO Curr...
Page 9: ...S0 pulse outputs are designed according to EN62053 31 DIN 83864 Pulse rate and pulse lengths can be configured by the keys Default settings ex factory 1 S0 Output Active Energy Import 12 13 2 S0 Outp...
Page 10: ...5 230 VAC or VDC max 90mA Rate per kWh kvarh 0 001 0 01 0 1 1 10 100 1000 10 000 Length Adjustable from 4 to 250 milliseconds in steps of 2 ms PEAK CONTROL THRESHOLD Threshold The following values can...
Page 11: ...conds until digits are not blinking 6 Red key to Unit Threshold 7 Push service key briefly 8 Select desired unit by blue key 9 Next by red key 10 Adjust Threshold by blue key 11 Go to next digit by re...
Page 12: ...place by using a 230VAC control signal In normal operation mode voltage is connected to input E1 input E2 is dead without voltage To start a new measurement period disconnect voltage from E1 and conne...
Page 13: ...an error message is displayed F F 0 00000000 No error meter ok F F 0 xxxxxxx0 Meter calibrated F F 0 xxxxxxx1 Meter not calibrated F F 0 xxxxxxx8 Calibration release meter is calibrated and can be re...
Page 14: ...t data are stored in non volatile EEPROM This takes place if voltage is falling below a defined level Also automatically every 24 hours to save all relevant data in non volatile EEPROM CALIBRATION PUL...
Page 15: ...ticount D5 3P 1 5A MID L1 L2 L3 N E4 NE control inputs S0 1 L1 L2 L3 N P1 P2 S1 S2 S1 S2 L1 S1 S2 L2 S1 S2 L3 N 6A P1 P2 S1 S2 P1 P2 S1 S2 5 4 3 2 1 6 7 8 9 10 11 12 13 14 15 L1 L2 L3 N L1 L1 L2 L2 L3...
Page 16: ...5 L1 L2 L3 N P1 P2 S1 S2 S1 S2 L1 S1 S2 L2 S1 S2 L3 N 6A P1 P2 S1 S2 P1 P2 S1 S2 B A control inputs multicount D5 2 ES 3P 1 5A MID 5 4 3 2 1 6 7 8 9 10 11 12 13 14 15 L1 L2 L3 N L1 L1 L2 L2 L3 L3 N E4...
Page 17: ...Am Kiefernschlag 7 D 91126 Schwabach T 49 0 9122 6373 0 F 49 0 9122 6373 83 E info kbr de www kbr de KBR Kompensationsanlagenbau GmbH...