63
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default
Value
F09.09
Special protection disposition selection
0
~
1111H
0
LED units digit: Distance of car uncontrolled protection derating judgment disposition.
0: prohibit
1: Enable
LED tens digit: one-key slip enable
0: prohibit
1: Enable
LED hundreds: poweron handling mode of terminal operation command
0: operation terminal is available at the undervoltage state, need trigger operation terminal to enable
runing command after bus-voltage normal.
1: operation terminal is available at the undervoltage state, only need keep operation terminal as the state
of electric level available, runing command can be enabled after bus-voltage normal.
LED thousands: Auto-reset enable for basic pole sealing error
0: Forbidden
1: Enable
6.11
V/F Control Parameters (Group F10)
Function Code
Name
Setting Range
Factory Default Value
F10.00
V/F curve setting
0
~
3
0
F10.01
V/F frequency 3
F10.03
~
F01.03
0.00Hz
F10.02
V/F voltage 3
F10.04
~
100%
0.0%
F10.03
V/F frequency 2
F10.05
~
F10.01
0.00Hz
F10.04
V/F voltage 2
F10.06
~
F10.02
0.0%
F10.05
V/F frequency 1
0.00
~
F10.03
0.00Hz
F10.06
V/F voltage 1
0
~
F10.04
0.0%
This group of parameters defines V/F setting modes of S610M to satisfy different load needs. According to
F10.00 definition, 3 fixed curves and 1 user-defined curve are available for choice.
When F10.00 = 1, it is 2.0 power reduced torque, shown as curve 1 in Figure 6-9;
When F10.00 = 2, it is 1.7 power reduced torque, shown as curve 2 in Figure 6-9;
When F10.00 = 3, it is 1.2 power reduced torque, shown as curve 3 in Figure 6-9.
The above mentioned curves are applicable to fan or pump type variable-torque load. Users may adjust the
curve setting according to the load characteristics to realize optimal energy saving results.