110
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Recommend set value
Remarks
beginning
F05.03
Rapid acceleration near
the end
0.6 m/s
3
F05.04
Deceleration
0.55 m/s
2
F05.05
Rapid deceleration at the
beginning
0.6 m/s
3
F05.06
Rapid deceleration near
the end
0.35 m/s
3
F05.07
Inspection acceleration
1.0 m/s
2
F05.08
Inspection deceleration
1.0 m/s
2
F05.14
Deceleration when stops
0.55 m/s
2
F07.01
Function selection of
input terminal X2
11
Operation contactor feedback input
F07.02
Function selection of
input terminal X3
12
Brake feedback input
F07.11
Input terminal activeness
setting
Set according to the
actual situation
Input terminal Normal
Open/Normal Close selection
F07.14
Output function of Relay
1
12
Operation contactor control output
F07.15
Output function of Relay
2
11
Brake control output
F07.16
Output function of Relay
3
7
Inverter error
F07.18
Output terminal
activeness setting
Set according to the
actual situation
Output terminal Normal
Open/Normal Close selection
F12.05
Baud rate of CAN
communication
Set according to the
actual situation
F12.08
Detection time of Can
communication overtime
(under CAN mode)
2.0s
Adjust according to practical
operation effect
7.6 Emergency operation mode during power outage
If power supply of the system is suddenly cut off during operation of the elevator, passengers may be locked
in the car. S610M inverter special for elevator has emergency operation mode in case of such situation.