Page 24
Katadyn
11.11
Local Setpoint
Precondition:
Setpoint must be set to LOCAL on the Screen “Setting”.
The amperage (mA) for silver ion (Ag+) dosing can bet set on the Screen “Overview” by entering the
Setpoint numerical or over the increase/decrease buttons.
Increases the Setpoint in 10mA up steps
Decreases the Setpoint in 10mA down steps
Numerical current (mA) Setpoint input.
If the option “Flow measurement” is activated and the control is set to
ppm, then the required dose* in ppm can be set by numerical input.
11.11.1
Remote Setpoint
Precondition:
Setpoint has to be set to REMOTE on the Screen “Setting”.
0-10VDC source connected to -X3:18/19/20 (see attachment 17.5 Electrical connection)
The 0-10VDC remote input corresponds to the 15-1000mA output to the activator
11.11.2
Dosage control
NOTE
Dose control is based on flow measurement and the law of Faraday and will
help to achieve a flow independent silver concentration in the process flow.
Measurements in regular intervals have to be conducted to ensure the correct
dosage.