7.1.3
Application drawings
The energy types E1…E16 are described by application examples below.
Application no. 1
❷
❺
Closed thermal system with 1 flow meter
Heat energy: E1 = V1 (t1-t2)k
t1:Inlet or t2:Outlet
Cooling energy: E3 = V1 (t2-t1)k
t1:Inlet or t2:Outlet
Flow sensor V1 is mounted in inlet or outlet as
selected during configuration.
Mass: M1 = V1 (Kmass t1) or
Mass: M1 = V1 (Kmass t2) depending on the
programming of inlet/outlet.
Config A = 3 (inlet) or 4 (outlet)
Application no. 2
❷
Closed thermal system with 2 identical flow meters
Leak monitoring and Permanent operational
monitoring
Billing energy: E1 = V1 (t1-t2)k
t1:Inlet
Control energy: E2 = V2 (t1-t2)k
t2:Outlet
t3 can be used for check measurement of either the
inlet or outlet temperature, but t3 is not used for
calculating the energy.
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t2)
Config. A = 3 (inlet)