
14
9.1.4 Prog. data RTC + 4…20 mA pulse inputs, type 67-00-22
The module has connection possibility for two pressure transmitters on terminals
57, 58 and 59 and can be adjusted for current reading or pressure range 6, 10 or 16
bar.
The module is prepared for remote reading, data from meter/module being
transferred to the system software via the external GSM/GPRS modem connected
on terminals 62, 63 and 64.
Furthermore, the module has two extra pulse inputs, VA and VB.
The module must be powered by 24 VAC.
9.1.5 Analog outputs, type 67-00-23
S
ee installation instructions 5512-369 (DK-GB-DE).
9.1.6 Lon Works, type 67-00-24
S
ee installation instructions 5512-396 (DK) or 5512-403 (GB)
.
9.1.7 Wireless M-Bus, type 67-00-30
The radio module has been designed to form part of the hand-held Wireless M-Bus
Reader systems of Kamstrup A/S at license-free radio frequency (868 MHz).
The module fulfils the C-mode specifications of prEN13757-4 and can thus form
part of other systems using Wireless M-Bus C-mode communication.
The radio module comes with internal antenna and external antenna connection as
well as two pulse inputs, which are identical with the previously described pulse
inputs.
The Wireless M-Bus radio transmitter is switched off on dispatch from the factory. It
turns on automatically when one litre of water has run through the meter. The radio
transmitter can also be switched on by means of a forced dial-up to the meter (keep
both front keys pressed for approx. 5 s. until CALL is displayed).
9.1.8 pulse inputs, type 67-00-60
The ZigBee module is used for wireless communication and can form part of a
remote reading system, in which several units can communicate with each other.
The pulse inputs of this module are identical with the previously described pulse
inputs.
The ZigBee module requires mains supply.
9.1.9 Metasys n2 + pulse inputs, type 67-00-62
The N2 module is used for data communication between meter and N2 Master in a
Johnson Controls System.
The RS485 port is galvanically separated from the meter.
The pulse inputs of this module are identical with the previously described pulse
inputs.
The N2 module requires mains supply.