Ultra
Assembly, installation and operating instructions
28
6.5.4 Ultra with KaControl module fitted, recirculating air
Voltage supply and alarm contact are factory-wired on the Ultra. In the event of an alarm message, the KaControl system
closes the valve and the fan is switched to stage 1.
Condensation pump
Fig. 12: Ultra for cooling
6.5.5 Commissioning and functional checks
Switch on the mains power.
Pour water into the condensate tray. The pump should switch on automatically and switch itself off again.
Test the alarm switch: Add water until the alarm switch is triggered (acoustic or visual warning message, fan switches
off or similar).